← All projects

Thermal systems

Steam Condenser: Thermal Design & CFD

Evaluated condenser configurations for a 105 MW heat-rejection requirement, comparing tube count and flow arrangement in ANSYS Fluent.

Past projectSummer 2026

Team design challenge · GE Vernova

Early shell-and-tube CAD model with internal baffles and a returning tube
Simplified shell-and-tube geometry used in the team’s initial CFD setup.

My contribution

I contributed to the GE Vernova team study, evaluating condenser concepts and comparing one- and two-tube, two-pass configurations at equal mass flow. The design work considered air versus water cooling, heat-transfer area, footprint, and pumping requirements.

Results & observations

Increasing tube count produced a predicted 32.6% heat-transfer improvement in the simplified CFD comparison. This supported the concept comparison; it did not establish the condensation performance of a full-scale 105 MW system.

A system-level choice

The challenge was to develop a condenser concept for a roughly 105 MW heat-rejection requirement. The study compared air and water cooling, then considered thermal surface area, footprint, pumping requirements, and a shell-and-tube arrangement.

Comparing configurations

Simplified ANSYS Fluent models compared materials, tube configurations, and baffle arrangements. The reported 32.6% heat-transfer difference applies to the modeled tube-count comparison at equal mass flow, not to a validated full-scale plant.

Beyond the contour plots

The analysis required defining fluid and metal domains, preparing a mesh, and revisiting inlet assumptions. The team also compared air and water cooling and developed a correlation-based capital-cost estimate. Those costs depend on assumed materials, dimensions, and correction factors; they are not supplier quotes.

Limits of the concept

The proposed full-scale design and the simplified CFD model are different levels of analysis. The simulation does not establish full-scale condensation performance. Fouling, vibration, water availability, and a validated phase-change model remain important follow-up work.

Tools & methods

  • ANSYS Fluent
  • Heat exchangers
  • CFD comparison
  • Thermal sizing
  • Flow distribution
  • Baffle arrangements
  • Material selection
  • Cooling-system tradeoffs

Technical documentation

Team presentation · PowerPoint